10kV 3-Core Heat Shrink Indoor Termination

  • High Voltage Withstand Performance:39KV power-frequency withstand voltage, suitable for high-voltage environments
  • Impulse Voltage Testing:Withstands 105KV impulse voltage, highly reliable
  • Partial Discharge Control:Discharge at 10KV is only 3PC, reducing cable losses
  • Load Cycling Capability:Withstands three cycles of heating and cooling at conductor temperatures, demonstrating strong stability
  • Negative Pole Voltage Endurance:Endures 52KV negative pole voltage for 15 minutes without flashover or breakdown
Get a Quote
Manual Download
Describe Display

The 10KV three-core heat shrink indoor terminal is a high-performance heat shrink accessory designed for the cable terminal section of high-voltage power systems. Using advanced heat shrink materials and technology, it provides excellent electrical insulation and mechanical protection, ensuring the cable operates stably in high-voltage environments. This product not only boasts outstanding voltage withstand capabilities but also endures frequent load cycling and impulse voltage tests, ensuring its long-term, reliable operation.

 

The 10KV three-core heat shrink indoor terminal has a power-frequency withstand voltage of up to 39KV and has undergone rigorous impulse voltage testing, withstanding 105KV without flashover or breakdown. In partial discharge tests, the discharge at 10KV is only 3PC, demonstrating excellent partial discharge control. Additionally, it has strong load cycling capabilities and can undergo three cycles of heating and cooling at conductor temperatures without performance degradation.

 

Product parameters
Power Frequency Withstand Voltage 39KV, 1MIN No Flashover or Breakdown
Partial Discharge Test 3PC at 10KV
Load Cycle (3 Cycles) 3 cycles at conductor temperature
Partial Voltage 3PC at 13KV
Impulse Voltage 105KV, No Flashover or Breakdown
Negative Polarity Voltage 52KV, 15MIN No Flashover or Breakdown
Long-Term Power Frequency Withstand Voltage 35KV, No Flashover or Breakdown
Size/Installation
10kV 3-Core Heat Shrink Indoor Termination Cross Section

 

Type Applicable Cable Cross-Section(mm²)
NSY-10/1.1 25~50
NSY-10/1.2 70~120
NSY-10/1.3 150~240
NSY-10/1.4 300~400
NSY-10/3.1 25~50
NSY-10/3.2 70~120
NSY-10/3.3 150~240
NSY-10/3.4 300~400