ZN63(VS1)-12 Indoor High Voltage Drawer-Type Vacuum Circuit Breaker

  • Frequent Operation Adaptability:Suitable for environments requiring frequent operations, ensuring efficient and safe system performance.
  • Strong Short-Circuit Protection:Rated short-circuit breaking current of up to 40kA, providing effective protection.
  • Integrated Design:Operating mechanism integrated with the breaker, simplifying installation and maintenance.
  • Compact and Maintenance-Free:Solid-sealed pole design reduces size and ensures maintenance-free operation.
  • Wide Environmental Adaptability:Operates reliably in temperatures from -10°C to 40°C and at altitudes up to 1000m.
  • High Mechanical Life:20,000 operations mechanical life, reducing maintenance needs.
Describe Display

The ZN63(VS1)-12 series vacuum circuit breaker is a high-voltage indoor switchgear designed for 11kV/12kV rated voltage and three-phase AC 50Hz electrical systems. It is widely used in industrial, mining, power plants, and substations for control and protection of electrical facilities. The device is designed in a drawer-type configuration, which can be used as a fixed installation unit or combined with a dedicated push mechanism for a drawer unit, catering to various installation and usage needs. The vacuum circuit breaker is known for its high reliability, durability, and low maintenance, making it especially suitable for environments requiring frequent operations.

 

Product parameters
Type ZN63(VS1)-12 Series
Rated Voltage 11kV/12kV
Operating Voltage 11kV/12kV
Rated Current 630A、1250A、1250A、1600A、2000A、2500A、3150A、4000A
Rated Short-Circuit Breaking Current(Rated Thermal Stable Current-RMS) 20/25kA、31.5kA、40kA
Rated Short-Circuit Making Current(Peak) 50/63kA、80kA、100kA
4s Rated Short-Circuit Withstand Current4s 20/25kA、31.5kA、40kA
Operating Withstand Voltage(Before/After Rated Breaking)/1min Power Frequency Withstand Voltage To Ground42(Across Break48)kV
Impulse Withstand Voltage(Before/After Rated Breaking)/Rated Lightning Impulse Withstand Voltage Peak To Ground75(Across Break85)kV
Rated Thermal Stable Time 4s
Rated Operating Sequence Open-0.3s-Close/Open-180s-Close/Open
Mechanical Life 20000Times
Rated Short-Circuit Breaking Current Interrupting Times 50Times
Operating Mechanism Rated Closing Voltage(DC) ACV、DCV、110V、220V
Contact Gap 11±1mm
Over-Travel(Contact Spring Compression Length) 3.5±0.5mm
Three-Phase Opening/Closing Bounce Time ≤2ms
Contact Closing Bounce Time ≤2ms
Average Opening Speed 0.9~1.2m/s
Average Closing Speed 0.5~0.8m/s
Opening Timeat Operating Voltage ≤0.05s
Opening Timeat Low Operating Voltage ≤0.08s
Closing Time 0.1s
Main Circuit Resistanceper Phase 630≤55μΩ、1250≤50μΩ
Allowable Cumulative Wear Thicknessof Moving/Stationary Contacts 3mm
Related Notes
Normal Service Conditions

 

Ambient Temperature: Not exceeding 40℃, not lower than -10℃ (storage and transportation at -30℃ is allowed).

 

Altitude: Not exceeding 1000m. (If used at higher altitudes, the rated insulation level shall be increased accordingly.)

 

Relative Humidity: Daily average ≤95%; daily average of saturated vapor pressure MPa; monthly average >1.8*10.

 

Seismic Intensity: Not exceeding magnitude 8.

 

Operating Environment: Locations free from fire, explosion, severe pollution, chemical corrosion, and violent vibration.

More Related Products
ZN63(VS1)-12 Indoor High Voltage Side-Mounted Vacuum Circuit Breaker
The ZN63(VS1)-12 series indoor side-mounted high-voltage vacuum circuit breaker ...
ZN63(VS1)-12 Series Indoor Fixed-Type High-Voltage Vacuum Circuit Breaker
The ZN63(VS1)-12 Series Indoor Fixed-Type High-Voltage Vacuum Circuit Breaker is...
ZW32-12 Outdoor High Voltage Vacuum Circuit Breaker
The ZW32-12 outdoor vacuum circuit breaker is designed for power systems with a ...
ZW7-40.5/35kV Outdoor High Voltage Vacuum Circuit Breaker
The ZW7-40.5/35kV series outdoor high-voltage vacuum circuit breaker (hereinafte...
Related News
Service & Support
Our certification team consists of 85+ engineers with more than 20 years of professional experience
24/7 Service. Average emergency response time is limited to less than 12 hours
Suitable for substations, industrial power grids, new energy projects and other demanding scenarios