GW5A-40.5 Outdoor High-Voltage Disconnecting Switch

  • Rated Voltage:Available in 35kV and 110kV rated voltages.
  • Strong Stability:Thermal stability current ≥ 2000kA, peak withstand current up to 300kA.
  • Wide Environmental Range:Operates in conditions up to 3000m altitude, temperatures between -25°C to 40°C, and wind speeds up to 35m/s.
  • Reliable Electrical Isolation:Ensures electrical isolation of high-voltage systems, enhancing equipment safety.
  • Protection Capabilities:Strong resistance to contamination and icing (up to 10mm), suitable for environments with pollution level III.
Get a Quote
Manual Download
Describe Display

The GW5A-40.5 outdoor high-voltage disconnecting switch is designed for use in 52Hz AC high-voltage power systems. It comes with rated voltages of 35kV and 110kV, providing the capability to open and close lines under no-load conditions. It is also used to electrically isolate high-voltage busbars, circuit breakers, and other electrical equipment from live high-voltage lines. The switch is also suitable for switching small capacitive or inductive currents. With strong thermal stability and high peak withstand currents, the device performs well even in high altitudes, extreme temperatures, and harsh environmental conditions.

Product parameters
Type GW5A-40.5
Maximum Voltage 35kV、110kV
Rated Current 630A、1000A、1250A
Thermal Stability Current ≥2000kA
Thermal Stability Time Fa=800s,Fb=200s
Peak Withstand Current 300kA
Features

Each pole of the disconnecting switch consists of two post insulators fixed on a common base at an included angle of 50°, forming a V-shaped configuration. The main components include: base assembly, post insulators, terminal block assembly, contact assembly, grounding blades, stationary grounding contacts, terminals, etc.

 

This disconnecting switch is available in three configurations: non-grounded, single-grounded, and double-grounded. A mechanical interlock is provided between the main shaft and grounding blades, with auxiliary switches included. The switch supports both manual and motorized operation modes.

Related Notes
Operating Environmental Conditions

 

Altitude ≤3000m;

Ambient temperature: Upper limit +40℃, lower limit -25℃;

Wind speed ≤35m/s;

Seismic intensity ≤8 magnitude;

Pollution level ≤Class III;

Ice coating thickness ≤10mm;

Installation locations must be free from flammable/explosive hazards, chemical corrosion, and severe vibration.