The 40.5kV Center Distance 400mm Conventional Embedded Pole is manufactured using advanced epoxy APG technology, embedding the vacuum interrupter and conductive elements into a compact and highly insulating structure. With current ratings from 1250A to 2500A, it is ideally suited for mid- and high-voltage vacuum circuit breakers and switchgear, supporting both fixed and withdrawable configurations. Widely used in utility grids, rail transit systems, and industrial power distribution networks.
Rated Voltage | 40.5kV |
Rated Current | 1250A, 1600A, 2000A, 2500A |
Rated Frequency | 50Hz |
Rated Short-Circuit Breaking Current | 25kA, 31.5kA |
Rated Short-Circuit Breaking Current Breaking Operations | 30 times |
Rated Short-Circuit Making Current | 80kA |
Rated Peak Withstand Current | 80kA |
Rated Short-Time Withstand Current (4s) | 25kA, 31.5kA |
Rated Single Capacitor Bank Breaking Current | 630A |
Rated Back-to-Back Capacitor Bank Breaking Current | 400A |
Short-Time (1min) Power Frequency Withstand Voltage | 95kV |
Lightning Impulse Withstand Voltage (Peak) | 185kV |
Circuit Resistance under Rated Contact Pressure | ≤25~30Ω |
Mechanical Life | 10,000 times |
Contact Self-closing Force | 200±60N |
Contact Reaction Force at Rated Opening Distance | 300±60N |
Permissible Contact Wear Thickness | 3mm |
Storage Period | 20 years |
Partial Discharge | ≤5pC |
Rated Operating Sequence | O-0.3s-CO-180s-CO |
Contact opening distance | 20±1mm |
Rated overtravel | 5±1mm |
Average opening speed | 1.7±0.2m/s |
Average closing speed | 0.75±0.2m/s |
Rated contact pressure | 3100±200N、3600±300N |
Contact closing bounce time | ≤3ms |
Contact opening and closing phase difference | ≤1ms |
Opening contact rebound amplitude | ≤2mm |