40.5KV Center Distance 472mm High-Altitude Pole

  • High-Altitude Optimization:472mm pole spacing ideal for high-elevation, low-pressure areas
  • Enhanced Insulation Strength:Withstands 137kV (power frequency), 267kV (impulse)
  • Wide Current Compatibility:Rated for 1250A to 2500A applications
  • Strong Fault Tolerance:31.5kA breaking current, 80kA peak withstand
  • Durable Mechanical Design:10,000 mechanical operations with high contact force
  • Reliable Insulation Integrity:Partial discharge ≤5pC ensures long-term safety
Get a Quote
Manual Download
Describe Display

The 40.5kV Center Distance 472mm High-Altitude Embedded Pole is engineered for high-altitude regions above 2000 meters and cold environments. Molded using high-insulation APG epoxy resin, it offers enhanced insulation distances and superior performance under reduced air pressure conditions. Ideal for substations and power distribution systems in plateau and harsh climates.

Product parameters
Rated Voltage 40.5kV
Rated Current 1250A, 1600A, 2000A, 2500A
Rated Frequency 50Hz
Rated Short-Circuit Breaking Current 31.5kA
Rated Short-Circuit Breaking Current Breaking Operations 30 times
Rated Short-Circuit Making Current 80kA
Rated Peak Withstand Current 80kA
Rated Short-Time Withstand Current (4s) 31.5kA
Rated Single Capacitor Bank Breaking Current 630A
Rated Back-to-Back Capacitor Bank Breaking Current 400A
Short-Time (1min) Power Frequency Withstand Voltage 137kV
Lightning Impulse Withstand Voltage (Peak) 267kV
Circuit Resistance under Rated Contact Pressure ≤25~30Ω
Mechanical Life 10,000 times
Contact Self-closing Force 250±60N
Contact Reaction Force at Rated Opening Distance 360±60N
Permissible Contact Wear Thickness 3mm
Storage Period 20 years
Partial Discharge ≤5pC
Rated Operating Sequence O-0.3s-CO-180s-CO

 

 

Parameters of Matching Vacuum Switch

 

Contact opening distance 20±2mm
Rated overtravel 5±1mm
Average opening speed 1.7±0.2m/s
Average closing speed 0.75±0.2m/s
Rated contact pressure 3600±300N
Contact closing bounce time ≤3ms
Contact opening and closing phase difference ≤2ms
Opening contact rebound amplitude ≤2mm