40.5KV Center Distance 400mm Standard Pole

  • Standard Structural Design:400mm center distance for broad compatibility
  • Wide Current Range:Rated for 1250A to 2500A, ideal for high-load systems
  • High Fault Capacity:Rated breaking current up to 31.5kA, peak withstand 80kA
  • Strong Insulation Performance:95kV power frequency, 185kV impulse withstand
  • Long Mechanical Life:10,000 operations for durable and frequent switching
  • Superior Insulation Integrity:Partial discharge ≤5pC ensures long-term reliability
Get a Quote
Manual Download
Describe Display

The 40.5kV Center Distance 400mm Standard Embedded Pole is molded with APG epoxy resin technology and tailored for compatibility with mainstream vacuum circuit breakers. It offers excellent insulation and mechanical durability, supporting rated currents from 1250A to 2500A. Designed for use in medium to high voltage distribution systems and industrial automation applications.

Product parameters
Rated Voltage 40.5kV
Rated Current 1250A, 1600A, 2000A, 2500A
Rated Frequency 50Hz
Rated Short-Circuit Breaking Current 25kA, 31.5kA
Rated Short-Circuit Breaking Current Breaking Operations 30 times
Rated Short-Circuit Making Current 80kA
Rated Peak Withstand Current 80kA
Rated Short-Time Withstand Current (4s) 25kA, 31.5kA
Rated Single Capacitor Bank Breaking Current 630A
Rated Back-to-Back Capacitor Bank Breaking Current 400A
Short-Time (1min) Power Frequency Withstand Voltage 95kV
Lightning Impulse Withstand Voltage (Peak) 185kV
Circuit Resistance under Rated Contact Pressure ≤25~30Ω
Mechanical Life 10,000 times
Contact Self-closing Force 200±60N
Contact Reaction Force at Rated Opening Distance 300±60N
Permissible Contact Wear Thickness 3mm
Storage Period 20 years
Partial Discharge ≤5pC
Rated Operating Sequence O-0.3s-CO-180s-CO

 

 

Parameters of Matching Vacuum Switch

 

Contact opening distance 20±1mm
Rated overtravel 5±1mm
Average opening speed 1.7±0.2m/s
Average closing speed 0.75±0.2m/s
Rated contact pressure 3100±200N、3600±300N
Contact closing bounce time ≤3ms
Contact opening and closing phase difference ≤1ms
Opening contact rebound amplitude ≤2mm