LW35-126 outdoor self-blasthigh-voltage SF₆ circuit breaker

  • Standard Voltage & Frequency: Suitable for 126kV power systems at AC 50Hz/60Hz.
  • Dual Control & Protection: Serves as both a protection device and interconnection breaker.
  • Multi-Standard Compliance: Conforms to GB, IEC, and specific technical specifications.
  • SF₆ Self-Blast Technology: Uses SF₆ as insulation and arc-extinguishing medium.
  • New Spring Mechanism: Equipped with a new-type spring operating mechanism.
  • High Performance: Features strong breaking capacity, low operating power, and high reliability.
Describe Display

The LW35-126 outdoor self-blast high-voltage SF₆ circuit breaker is suitable for AC 50Hz (60Hz), 126kV power systems. It serves as a control and protection device for power systems, and can also be used as an interconnection circuit breaker.

 

The circuit breaker complies with the requirements of GB1984-2003 High-Volotage AC Circyit Breakers , IEC62271-100-2001 High-Volotage AC Circyit Breakers, and Technical Specifications for LW35-126 Self-Blast Circuit Breakers. Using SF₆ gas as insulation and arc-extinguishing medium and adopting the self-blast arc extinguishing principle, the circuit breaker is equipped with a new-type spring operating mechanism. It features strong breaking capacity, low operating power, and high reliability.

Product parameters
No. Item Unit Parameter  
      LW35-126W/T3150-40(Normal) LW35-126W/T3150-31.5(H),(For high-altitude areas)
1 Applicable environment - Normal High-altitude areas- High-altitude applicable
2 Rated voltage kV 126/145 126/145
3 Rated power-frequency withstand voltage (1min) kV To ground:K・230;
Between breaks:K・(230+73)
 
4 Rated lightning impulse withstand voltage kV To ground:K・550;
Between breaks:K・(550+103)
 
5 Power-frequency withstand voltage at zero SF₆ gas pressure (5min) kV 95  
6 Rated frequency Hz 50 (60)  
7 Rated current A 3150  
8 First-level series number - 1.5  
9 Rated short-circuit breaking current kA 40 31.5
10 Rated short-circuit making current (peak) kA 100 80
11 Rated short-time withstand current kA 40 31.5
12 Rated peak withstand current kA 100 80
13 Rated short-circuit duration s 4 8
14 Rated out-of-step breaking current kA 10  
15 Proximity fault breaking current kA 90% Ik​, 75% Ik​  
16 Rated line-charging switching current A 31.5  
17 Rated operating sequence - O-0.3s-CO-180s-CO  
18 Main circuit resistance μΩ ≤65  
19 Rated SF₆ gas pressure (20°C gauge pressure) MPa 0.6 0.45
20 Alarm minimum functional pressure (20°C gauge pressure)* MPa 0.55±0.015/0.50±0.015 0.40±0.015/0.34
21 Annual SF₆ gas leakage rate % ≤0.5  
22 SF₆ gas moisture content (V/V) ppm ≤150  
23 Mechanical life - 6000/10000  
24 Radio interference level μV ≤500  
25 Creepage distance mm Between breaks:3906/3150;
To ground:3906/3150
 
26 SF₆ gas charge per unit kg 8  

 

No. Item Unit Parameter
1 Auxiliary circuit voltage V DC220 or AC220, DC110, DC48
2 Opening coil voltage/current V/A DC110/4; DC220/2; AC220/5; DC48/4
3 Closing coil voltage/current V/A DC110/4; DC220/1.3; AC220/5; DC48/4
4 Energy storage motor - -
  Rated voltage V DC220 or AC220, DC110, DC48
  Normal operating voltage range V 85%~110%
  Power W 720
5 Motor energy storage time s ≤20
6 Heater and lighting circuit voltage V AC220
7 Auxiliary switch rated voltage V DC220 or AC380
8 Auxiliary switch rated current A 10
9 Auxiliary switch contacts - 11 normally open + 11 normally closed

 

No. Item Unit Parameter
1 Center distance between circuit breaker poles mm 1700
2 Moving contact stroke mm 120 + 30
3 Moving contact contact stroke mm 25 + 30
4 Operating linkage stroke between breakers (chord length) mm 110 + 30
5 Opening speed m/s 5.0±0.5
6 Closing speed m/s 3.0±0.5
7 Opening time ms ≤40
8 Closing time ms 70±8
9 Breaking time ms ≤60
10 Close-open time ms 35~50
11 Open-close time ms 300
12 Three-phase opening asynchronism (time difference) ms ≤2
13 Three-phase closing asynchronism (time difference) ms ≤3
Features

The circuit breaker adopts a three-phase porcelain-column support structure (outdoor design), with three phases sharing one SRCT36-C spring operating mechanism (arranged centrally, with three-phase linkage), giving it a sleek and sophisticated appearance. Using SF₆ gas as insulation and arc-extinguishing medium, the SF₆ gas paths of the three phases are connected during operation, and a pointer type density relay is used to monitor its pressure and density. Thanks to the adoption of the self-blast arc-extinguishing principle and optimized design of the circuit breaker's motion system, mechanical efficiency is effectively improved, and operating power is minimized

 

Application

 

The normal operating environment complies with GB/T11022-1999 Common Technical Requirements for High-Voltage Switchgear and Controlgear Standards, i.e.:a. Ambient temperature: -40°C ~ +40°C;b. Altitude: not exceeding 3000m;c. Wind speed: not greater than 34m/s;d. Daily temperature difference: not greater than 25°C;e. Solar radiation: not greater than 0.1W/cm2;f. Monthly average relative humidity: not greater than 90%;g. Seismic acceleration: horizontal s0.5g, verticals0.38g;h. Ice coating thickness: not greater than 10mm;i. Air pollution degree: not exceeding Class IV in GB5582;j. Installation site: Outdoor. If users have special requirements for the operating environment, please negotiatel separately with the manufacturer.

More Related Products
ZN63(VS1)-12 Indoor High Voltage Drawer-Type Vacuum Circuit Breaker
The ZN63(VS1)-12 series vacuum circuit breaker is a high-voltage indoor switchge...
ZN63(VS1)-12 Indoor High Voltage Side-Mounted Vacuum Circuit Breaker
The ZN63(VS1)-12 series indoor side-mounted high-voltage vacuum circuit breaker ...
ZN85-40.5 Indoor High Voltage Vacuum Circuit Breaker
The ZN85-40.5 series indoor high-voltage vacuum circuit breaker (hereinafter ref...
ZW32-12 Outdoor High Voltage Vacuum Circuit Breaker
The ZW32-12 outdoor vacuum circuit breaker is designed for power systems with a ...
Related News
Service & Support
Our certification team consists of 85+ engineers with more than 20 years of professional experience
24/7 Service. Average emergency response time is limited to less than 12 hours
Suitable for substations, industrial power grids, new energy projects and other demanding scenarios